7. COMMUNICATION DATA LIST
IMR01Y36-E2
64
Continued from the previous page.
ID
Name
Number
of data
items
Attri-
bute
Data range
Factory
set value
133
(0x0085)
Event 4 hold action
64
R/W 0: OFF
1: Hold action ON
(when power turned on; when
transferred from STOP to RUN)
2: Re-hold action ON
(when power turned on; when
transferred from STOP to RUN;
SV
changed)
This function is validated when input value,
deviation or manipulated value action has
been selected.
In case of a deviation action, this function
is not available while in Remote mode and
while Setting changing rate limiter is
working.
Based on
model code.
When not
specifying: 0
134
(0x0086)
Event 4 interlock
64
R/W 0: Unused
1: Used
0
135
(0x0087)
Event 4 differential gap
64
R/W
c
Deviation, Process, Set value or
Deviation action between channels:
0 to Input span (Unit:
°
C [
°
F])
d
MV: 0.0 to 110.0 %
Becomes invalidated when the Event 4
type corresponds to “9: Control loop break
alarm (LBA).”
c
1
d
1.0
136
(0x0088)
Event 4 delay timer
64
R/W 0 to 18000 seconds
0
137
(0x0089)
Force ON of Event 4
action
64 R/W
Bit data
Bit 0: Event output turned on at input
error occurrence
Bit 1: Event output turned on in Manual
mode
Bit 2: Event output turned on during the
Autotuning (AT) function is being
executed
Bit 3: Event output turned on during the
Setting change rate limiter is being
operated
Bit 4 to Bit 15: Unused
Data 0: Invalidate
1: Validate
[Decimal number: 0 to 15]
0
138
(0x008A)
CT ratio
64
R/W 0 to 9999
CTL-6-P-N:
800
CTL-12-S56-
10L-N: 1000
139
(0x008B)
CT assignment
64
R/W 0: None
1: OUT1
2: OUT2
3: OUT3
4: OUT4
1
Continued on the next page.