7. COMMUNICATION DATA LIST
IMR01Y36-E2
79
7.4 Z-DIO Module Object (0x66: 66Hex)
ID
Name
Number
of data
items
Attri-
bute
Data range
Factory
set value
1
(0x0001)
Digital input (DI) state
16
RO Bit data
Bit 0: DI1 state
Bit 5: DI6 state
Bit 1: DI2 state
Bit 6: DI7 state
Bit 2: DI3 state
Bit 7: DI8 state
Bit 3: DI4 state
Bit 8 to Bit 15:
Bit 4: DI5 state
Unused
Data 0: Contact open
1: Contact closed
[Decimal number: 0 to 255]
⎯
2
(0x0002)
Digital output (DO) state
16
RO Bit data
Bit 0: DO1 state
Bit 5: DO6 state
Bit 1: DO2 state
Bit 6: DO7 state
Bit 2: DO3 state
Bit 7: DO8 state
Bit 3: DO4 state
Bit 8 to Bit 15:
Bit 4: DO5 state
Unused
Data 0: OFF
1: ON
[Decimal number: 0 to 255]
⎯
3
(0x0003)
Error code
16 RO Bit
data
Bit 1: Data back-up error
Bit 0, Bit 2 to Bit 15: Unused
Data 0: OFF
1: ON
[Decimal number: 0 to 2]
⎯
4
(0x0004)
Integrated operating time
monitor
16 RO 0 to 19999 hours
⎯
5
(0x0005)
Backup memory state
monitor
16 RO 0: The content of the backup memory
does not coincide with that of the RAM.
1: The content of the backup memory
coincides with that of the RAM.
⎯
6
(0x0006)
RUN/STOP transfer
16
R/W 0: STOP (Control stop)
1: RUN (Control start)
0
7
(0x0007)
DO manual output
16
R/W Bit data
Bit 0: DO1 manual output
Bit 1: DO2 manual output
Bit 2: DO3 manual output
Bit 3: DO4 manual output
Bit 4: DO5 manual output
Bit 5: DO6 manual output
Bit 6: DO7 manual output
Bit 7: DO8 manual output
Bit 8 to Bit 15: Unused
Data 0: OFF
1: ON
[Decimal number: 0 to 255]
0
8
(0x0008)
DO output distribution
selection
128 R/W 0:
DO
output
1: Distribution output
0
9
(0x0009)
DO output distribution
bias
128 R/W
−
100.0 to
+
100.0 %
0.0
10
(0x000A)
DO output distribution
ratio
128 R/W
−
9.999 to
+
9.999 1.000
Continued on the next page.