7. COMMUNICATION DATA LIST
IMR01Y36-E2
71
Continued from the previous page.
ID
Name
Number
of data
items
Attri-
bute
Data range
Factory
set value
ID211 to ID224 are Engineering setting data. [Writable in the STOP mode]
211
(0x00D3)
Automatic temperature
rise dead time
♣
64
R/W 0.1 to 1999.9 seconds
10.0
212
(0x00D4)
Automatic temperature
rise gradient data
♣
64
R/W 0.1 to Input span/minutes
Varies with the setting of the Decimal
point position selection.
1.0
213
(0x00D5)
Unused
⎯
⎯
⎯
⎯
214
(0x00D6)
Setting change rate limiter
unit time
64
R/W 1 to 3600 seconds
60
215
(0x00D7)
Soak time unit
64
R/W 0: 0 to 5999 minutes
[0 hours 00 minutes to
99 hours 59 minutes]
1: 0 to 11999 seconds
[0 minutes 00 seconds to
199 minutes 59 seconds:]
Set the data range of Memory area soak
time monitor and Area soak time.
1
216
(0x00D8)
Setting limiter high
64
R/W Setting limiter low to Input scale high
Input scale high
217
(0x00D9)
Setting limiter low
64
R/W Input scale low to Setting limiter high
Input scale low
218
(0x00DA)
PV transfer function
♣
64
R/W 0: Unused
1: Used
0
219
(0x00DB)
Unused
⎯
⎯
⎯
⎯
•
•
•
224
(0x00E0)
ID225 to ID235 are normal setting data.
225
(0x00E1)
Controller state 1
31
RO Bit data
Z-TIO module:
Bit 0: Burnout state
Bit 1: Unused
Bit 2: Event 1 state
Bit 3: Event 2 state
Bit 4: Event 3 state
Bit 5: Event 4 state
Bit 6: Heater break alarm (HBA) state
Bit 7 to Bit 15: Unused
OR
data for each Z-TIO module.
Z-DIO module:
Bit 0 to Bit 15: Unused
Data 0: OFF
1: ON
[Decimal number: 0 to 125]
⎯
♣
Parameters only used for Heat/Cool PID control or position proportioning control, therefore data for CH2 and
CH4 of Z-TIO modules are unused.
Continued on the next page.