7. COMMUNICATION DATA LIST
IMR01Y36-E2
54
Continued from the previous page.
ID
Name
Number
of data
items
Attri-
bute
Data range
Factory
set value
51
(0x0033)
Integral time
[cool-side]
★
♣
64 R/W 0 to 3600 seconds or
0.0 to 1999.9 seconds (0, 0.0: PD action)
Varies with the setting of the
Integral/Derivative time decimal point
position selection.
If control is other than Heat/Cool PID
control, set to RO (Only reading data is
possible).
240
52
(0x0034)
Derivative time
[cool-side]
★
♣
64 R/W 0 to 3600 seconds or
0.0 to 1999.9 seconds (0, 0.0: PI action)
Varies with the setting of the
Integral/Derivative time decimal point
position selection.
If control is other than Heat/Cool PID
control, set to RO (Only reading data is
possible).
60
53
(0x0035)
Overlap/Deadband
★
♣
64 R/W TC/RTD inputs:
−
Input span to +Input span
(Unit:
°
C [
°
F])
Voltage (V)/Current (I) inputs:
−
100.0 to +100.0 % of Input span
Minus (
−
) setting results in Overlap.
However, the overlapping range is within
the proportional range.
If control is other than Heat/Cool PID
control, set to RO (Only reading data is
possible).
0
54
(0x0036)
Manual reset
★
64
R/W
−
100.0 to +100.0 %
If the Integral function is validated, set to
RO (Only reading data is possible).
When integral action (heating or cooling
side) is zero, manual reset value is added to
the control output.
0.0
55
(0x0037)
Setting change rate limiter
(up)
★
64 R/W 0 (0.0) to Input span/unit time *
(0 (0.0): Unused)
0 (0.0)
56
(0x0038)
Setting change rate limiter
(down)
★
64 R/W
* Unit time: 60 seconds
(factory set value)
0 (0.0)
57
(0x0039)
Area soak time
★
64
R/W 0 minutes 00 seconds to
199 minutes 59 seconds:
0 to 11999 seconds
0 hours 00 minutes to
99 hours 59 minutes:
0 to 5999 minuts
Data range of Area soak time can be
selected on the Soak time unit.
0
58
(0x003A)
Link area number
★
64
R/W 0 to 8
(0: No link)
0
★
: Data related to multi-memory area function
It is possible to change only the data of the control area which is selected by the memory area transfer (ID: 37).
♣
Parameters only used for Heat/Cool PID control or position proportioning control, therefore data for CH2 and
CH4 of Z-TIO modules are unused.
Continued on the next page.