8. USAGE EXAMPLE
IMR01Y36-E2
85
8.3 Setting of Use Instruments
Setting of the PLC, COM-JH and controller is shown in the following.
PLC setting
[DeviceNet communication requirement]
•
Node address:
0
•
DeviceNet communication speed: 125 kbps
•
Unit number:
0
•
Communication cycle time:
(Number of COM-JH communication words
×
1.2
+
50) [ms]
or more
=
13
×
1.2
+
50
=
65.6 [ms] or more
For setting procedure, refer to
PLC Instruction Manual.
COM-JH setting
[DeviceNet communication requirement]
•
Node address:
1
•
DeviceNet communication speed:
125 kbps
•
Number of communication data items: 13 words
•
Controller address:
1, 2 (Module address 1 and Module address 2)
•
Action mode:
0
(Address setting method Continuous setting, PID/AT transfer by Polling I/O communication: Invalidate)
•
Automatic acquisition of controller address: 0: Do not execute the automatic acquisition
For setting procedure, refer to
5. SETTING (P. 20)
and
6.2 Communication Method (P. 27)
.
[Controller communication requirement]
•
Communication speed:
19200 bps
For setting procedure, refer to
5.3 DIP Switch Setting
(P. 22)
.
Controller (SRZ Z-TIO-A module) setting
•
Module address:
1 (Address setting switch: 0) and 2 (Address setting switch: 1)
•
Communication protocol:
Modbus-RTU
•
Communication speed:
19200 bps (factory set value)
•
Data bit configuration:
Data 8-bit, without parity, stop 1-bit
For setting procedure, refer to
Z-TIO Host Communication Quick Instruction Manual
(IMS01T02-E )
.