7. COMMUNICATION DATA LIST
IMR01Y36-E2
80
Continued from the previous page.
ID
Name
Number
of data
items
Attri-
bute
Data range
Factory
set value
11
(0x000B)
DO proportional cycle
time
128
R/W 0.1 to 100.0 seconds
Relay contact
output: 20.0
Open collector
output: 2.0
12
(0x000C)
DO minimum ON/OFF
time of proportioning cycle
128
R/W 0 to 1000 ms
0
After ID13 are engineering setting data. [Writable in the STOP mode]
13
(0x000D)
DI function assignment
16
R/W 0 to 29
(Refer to P. 81)
Based on
model code.
When not
specifying: 0
14
(0x000E)
Memory area setting signal
16
R/W 0: Validate
1: Invalidate
1
15
(0x000F)
DO signal assignment
module address 1
16 R/W
−
1
16
(0x0010)
DO signal assignment
module address 2
16 R/W
−
1, 0 to 99
When “-1” is selected, all of the signals of
the same type (except temperature rise
completion and DO manual output value)
are
OR
-operated and produced as outputs
from DO.
−
1
17
(0x0011)
DO output assignment 1
[DO1 to DO4]
16
R/W 0 to 13
(Refer to P. 82)
Based on
model code.
When not
specifying: 0
18
(0x0012)
DO output assignment 2
[DO5 to DO8]
16 R/W 0 to 13
(Refer to P. 82)
Based on
model code.
When not
specifying: 0
19
(0x0013)
DO
energized/de-energized
128 R/W 0: Energized
1: De-energized
0
20
(0x0014)
DO output distribution
master channel module
address
128 R/W
−
1
(Master channel is selected from itself)
0 to 99
(Master channel is selected from other modules)
−
1
21
(0x0015)
DO output distribution
master channel selection
128 R/W 1 to 99
1
22
(0x0016)
DO manipulated output
value (MV) at STOP mode
128 R/W
−
5.0 to
+
105.0 %
−
5.0
23
(0x0017)
DO output limiter (high)
128
R/W DO output limiter (low) to 105.0 %
105.0
24
(0x0018)
DO output limiter (low)
128
R/W
−
5.0 % to DO output limiter (high)
−
5.0
25
(0x0019)
Control RUN/STOP
holding setting
16 R/W 0: Not holding (STOP start)
1: Holding (RUN/STOP hold)
1
26
(0x001A)
Interval time
16
R/W 0 to 250 ms
10
27
(0x001B)
Unused
⎯
⎯
⎯
⎯
•
•
•
255