7. COMMUNICATION DATA LIST
IMR01Y36-E2
76
Continued from the previous page.
ID
Name
Number
of data
items
Attri-
bute
Data range
Factory
set value
14
(0x000E)
EDS transfer time
(for disturbance 1)
64 R/W
0
15
(0x000F)
EDS transfer time
(for disturbance 2)
64 R/W
0 to 3600 seconds or
0.0 to 1999.9 seconds
0
16
(0x0010)
EDS action time
(for disturbance 1)
64 R/W
600
17
(0x0011)
EDS action time
(for disturbance 2)
64 R/W
1 to 3600 seconds
600
18
(0x0012)
EDS action wait time
(for disturbance 1)
64
R/W 0.0 to 600.0 seconds
0.0
19
(0x0013)
EDS action wait time
(for disturbance 2)
64 R/W
0.0
20
(0x0014)
EDS value learning times
64
R/W 0 to 10 times (0: No learning mode)
1
21
(0x0015)
EDS start signal
64
R/W 0: EDS start signal OFF
1: EDS start signal ON (for disturbance 1)
2: EDS start signal ON (for disturbance 2)
0
22
(0x0016)
Operation mode
64
R/W 0: Unused
1: Monitor
2: M Event function
3: Control
3
23
(0x0017)
Communication switch for
logic
16 R/W Bit
data
Bit 0: Communication switch 1
Bit 1: Communication switch 2
Bit 2: Communication switch 3
Bit 3: Communication switch 4
Bit 4 to Bit 15: Unused
Data 0: OFF
1: ON
[Decimal number: 0 to 15]
0
After ID24 are Engineering setting data. [Writable in the STOP mode]
24
(0x0018)
Event 1 channel setting
64
R/W
1
25
(0x0019)
Event 2 channel setting
64
R/W
1
26
(0x001A)
Event 3 channel setting
64
R/W
1
27
(0x001B)
Event 4 channel setting
64
R/W
1: Channel 1
2: Channel 2
3: Channel 3
4: Channel 4
This function is validated when “Deviation
between channels” is selecte
d
1
28
(0x001C)
EDS transfer time decimal
point position
♣
64 R/W 0: 1 second setting (No decimal place)
1: 0.1 seconds setting (One decimal place)
0
29
(0x001D)
Output average processing
time for EDS
♣
64
R/W 0.1 to 200.0 seconds
1.0
♣
Parameters only used for Heat/Cool PID control or position proportioning control, therefore data for CH2 and
CH4 of Z-TIO modules are unused.
Continued on the next page.