7. COMMUNICATION DATA LIST
IMR01Y36-E2
65
Continued from the previous page.
ID
Name
Number
of data
items
Attri-
bute
Data range
Factory
set value
140
(0x008C)
Heater break alarm (HBA)
type
64 R/W 0: Heater break alarm (HBA) type A
(Time-proportional control output)
1: Heater break alarm (HBA) type B
(Continuous control output)
Based on
model code
141
(0x008D)
Number of heater break
alarm (HBA) delay times
64
R/W 0 to 255 times
5
142
(0x008E)
Unused
⎯
⎯
⎯
⎯
•
•
•
145
(0x0091)
146
(0x0092)
Hot/Cold start
64
R/W 0: Hot start 1
1: Hot start 2
2: Cold start
0
147
(0x0093)
Start determination point
64
R/W 0 to Input span
(The unit is the same as input value.)
(0: Action depending on the Hot/Cold
start selection)
Based on
specifications.
148
(0x0094)
Unused
⎯
⎯
⎯
⎯
149
(0x0095)
Unused
⎯
⎯
⎯
⎯
150
(0x0096)
SV tracking
64
R/W 0: Unused
1: Used
1
151
(0x0097)
MV transfer function
[Action taken when
changed to Manual mode
from Auto mode]
64 R/W 0: MV in Auto mode is used.
[Balanceless-bumpless function]
1: MV in previous Manual mode is used.
0
152
(0x0098)
Control action
64
R/W 0: Brilliant II PID control (direct action)
1: Brilliant II PID control (reverse action)
2: Brilliant II Heat/Cool PID control
[water
cooling]
3: Brilliant II Heat/Cool PID control
[air
cooling]
4: Brilliant II Heat/Cool PID control
[Cooling gain linear type]
5: Position proportioning control
Odd channel: From 0 to 5 can be set.
Even channel: Only 0 or 1 can be set. *
* In Heat/Cool PID control and Position
proportioning control, control action is
not performed. Only PV monitor and
event action is performed.
Based on
model code.
When not
specifying: 1
153
(0x0099)
Integral/Derivative time
decimal point position
♣
64
R/W 0: 1 second setting (No decimal place)
1: 0.1 seconds setting
(One decimal place)
0
♣
Parameters only used for Heat/Cool PID control or position proportioning control, therefore data for CH2 and
CH4 of Z-TIO modules are unused.