7. COMMUNICATION DATA LIST
IMR01Y36-E2
50
7.2 Z-TIO Module Object (0x64: 64Hex)
ID
Name
Number
of data
items
Attri-
bute
Data range
Factory
set value
1
(0x0001)
Measured value (PV)
64
RO Input scale low to Input scale high
⎯
2
(0x0002)
Current transformer (CT)
input value monitor
64 RO CTL-6-P-N:
0.0 to 30.0 A
CTL-12-S56-10L-N: 0.0 to 100.0 A
⎯
3
(0x0003)
Unused
⎯
⎯
⎯
⎯
4
(0x0004)
Set value (SV) monitor
64
RO Setting limiter low to Setting limiter high
⎯
5
(0x0005)
Remote setting (RS) input
value monitor
64
RO Setting limiter low to Setting limiter high
⎯
6
(0x0006)
Burnout state monitor
64
RO 0: OFF
1: ON
⎯
7
(0x0007)
Unused
⎯
⎯
⎯
⎯
8
(0x0008)
Event 1 state monitor
64
RO
⎯
9
(0x0009)
Event 2 state monitor
64
RO
⎯
10
(0x000A)
Event 3 state monitor *
64
RO
⎯
11
(0x000B)
Event 4 state monitor
64
RO
0: OFF
1: ON
* If the Event 3 type is temperature rise
completion, check the temperature rise
completion state in the comprehensive
event state [Z-TIO module extended
object (0x65: 65Hex) ID: 1].
(The Event 3 state monitor does not turn
ON.)
⎯
12
(0x000C)
Heater break alarm (HBA)
state monitor
64 RO 0: OFF
1: ON
⎯
13
(0x000D)
Unused
⎯
⎯
⎯
⎯
14
(0x000E)
Manipulated output value
(MV) monitor [heat-side]
♣
64 RO PID control or Heat/Cool PID control:
−
5.0 to +105.0 %
Position proportioning control with
feedback resistance (FBR) input:
0.0 to 100.0 %
⎯
15
(0x000F)
Manipulated output value
(MV) monitor [cool-side]
♣
64 RO
−
5.0 to +105.0 %
⎯
16
(0x0010)
Error code
64
RO Bit data
Bit 0:
Adjustment data error
Bit 1:
Data back-up error
Bit 2:
A/D conversion error
Bit 3, Bit 4: Unused
Bit 5:
Logic output data error
Bit 6 to Bit 15: Unused
Data
0: OFF
1: ON
[Decimal number: 0 to 63]
⎯
17
(0x0011)
Unused
⎯
⎯
⎯
⎯
♣
Parameters only used for Heat/Cool PID control or position proportioning control, therefore data for CH2 and
CH4 of Z-TIO modules are unused.