7. COMMUNICATION DATA LIST
IMR01Y36-E2
62
Continued from the previous page.
ID
Name
Number
of data
items
Attri-
bute
Data range
Factory
set value
126
(0x007E)
Event 3 type
64
R/W 0: None
1: Deviation high
(SV monitor value used)
1
2: Deviation low
(SV monitor value used)
1
3: Deviation high/low
(SV monitor value used)
1
4: Band (SV monitor value used)
1
5: Process high
1
6: Process low
1
7: SV high
8: SV low
9: Temperature rise completion
10: MV high [heat-side]
1,
2
11: MV low [heat-side]
1,
2
12: MV high [cool-side]
1
13: MV low [cool-side]
1
14: Deviation high
(Local SV value used)
1
15: Deviation low
(Local SV value used)
1
16: Deviation high/low
(Local SV value used)
1
17: Deviation (Local SV value used)
1
18: Deviation between channels high
1
19: Deviation between channels low
1
20: Deviation between channels
high/low
1
21: Deviation between channels band
1
1
Event hold action is available.
2
If there is Feedback resistance (FBR)
input in Position proportioning control,
set to the Feedback resistance (FBR)
input value.
Based on
model code.
When not
specifying: 0
127
(0x007F)
Event 3 hold action
64
R/W 0: OFF
1: Hold action ON
(when power turned on; when
transferred from STOP to RUN)
2: Re-hold action ON
(when power turned on; when
transferred from STOP to RUN;
SV
changed)
This function is validated when input value,
deviation or manipulated value action has
been selected.
In case of a deviation action, this function
is not available while in Remote mode and
while Setting changing rate limiter is
working.
Based on
model code.
When not
specifying: 0
128
(0x0080)
Event 3 interlock
64
R/W 0: Unused
1: Used
0
129
(0x0081)
Event 3 differential gap
64
R/W
c
Deviation, Process, Set value or
Deviation action between channels:
0 to Input span (Unit:
°
C [
°
F])
d
MV: 0.0 to 110.0 %
c
1
d
1.0
Continued on the next page.