7. COMMUNICATION DATA LIST
IMR01Y36-E2
70
Continued from the previous page.
ID
Name
Number
of data
items
Attri-
bute
Data range
Factory
set value
ID204 is normal setting data.
204
(0x00CC)
Startup tuning (ST)
64
R/W 0: Startup tuning (ST) unused
1: Execute once *
2: Execute always
* When the Startup tuning (ST) is finished,
the setting will automatically returns to
“0: ST unused.”
The Startup tuning (ST) function is
activated according to the ST start
condition selected.
If control is other than Position
proportioning control, set to RO (Only
reading data is possible).
0
ID205 to ID209 are Engineering setting data. [Writable in the STOP mode]
205
(0x00CD)
ST proportional band
adjusting factor
♣
64 R/W
1.00
206
(0x00CE)
ST integral time adjusting
factor
♣
64 R/W
1.00
207
(0x00CF)
ST derivative time
adjusting factor
♣
64 R/W
0.01 to 10.00 times
1.00
208
(0x00D0)
ST start condition
♣
64
R/W 0: Activate the Startup tuning (ST)
function when the power is turned on;
when transferred from STOP to RUN;
or when the Set value (SV) is changed.
1: Activate the Startup tuning (ST)
function when the power is turned on;
or when transferred from STOP to
RUN.
2: Activate the Startup tuning (ST)
function when the Set value (SV) is
changed.
0
209
(0x00D1)
Automatic temperature
rise group
♣
64 R/W 0 to 16
(0: Automatic temperature rise function
OFF)
0
ID210 is normal setting data.
210
(0x00D2)
Automatic temperature
rise learning
64 R/W 0: Unused
1: Learning *
* When the automatic temperature rise
learning is finished, the setting will
automatically returns to “0: Unused.”
If the Automatic temperature rise group
corresponds to “0: Automatic temperature
rise function OFF,” set to RO (Only
reading data is possible).
1
♣
Parameters only used for Heat/Cool PID control or position proportioning control, therefore data for CH2 and
CH4 of Z-TIO modules are unused.
Continued on the next page.