CONTROL CONNECTION
79
Pulse Output Signals Connection in IP66 Drives
In IP66 drives, the pulse output signal is shared with the Q1 terminal. This
terminal must be set as TO in the parameter G6.33 and the next
connections must be performed to use it as a train pulse output:
•
Connect a 1/4W, 560Ω resistor between VR and Q1
terminals.
•
Connect EG and CM terminals.
Recommended Cable Section
The recommended wire characteristics are summarized in the table below.
The wire length of the safety input should not exceed 30m.
Terminal Type
Recommended wire size [mm
2
]
(AWG)
Screw
Torque
[N.m]
No crimp-style
terminal
Crimp-style
terminal
P1
–
P7, CM
0.75 (18)
0.5 (20)
M2 (1/32“)
0.22 ~ 0.25
VR
V1
I2
AO
Q1
EG
24
TI
TO
SA, SB, SC
S+, S-, SG
A1, B1, C1
1.0 (17)
1.5 (15)
M2.6 (3/32“)
0.4
A2, C2