POWER ELECTRONICS
SD300
DESCRIPTION OF PROGRAMMING PARAMETERS
123
Screen Description Default
value
Range
Function
Set
on
RUN
bA.20
Auto tuning
None
0 to 7
NOTE:
Comes from the previous page.
OPT. DESCR. FUNCTION
6
Tr
Measures the rotor time
constant (Tr) with the
motor in the stopped
position and Control Mode
dr.9 is set to ‘Sensorless’.
7
All PM
The autotuning is activated
for permanent magnet
synchronous motors.
bA.21
Stator
Resistor
0 (*)
(*)
Stator resistor fine setting.
NO
bA.22
Leak
Inductor
0mH (*)
(*)
Leak inductor fine setting.
NO
bA.23
Stator
Inductor
0mH (*)
(*)
Inductor stator fine setting.
NO
bA.24
[3]
Rotor Time
Const
145ms 25 to 5000ms Rotor time constant fine setting.
NO
bA.25
Stator
inductance
scale.
100%
50 to 150% Set stator inductance scale.
NO
bA.26
Rotor time
constant
scale.
100%
50 to 150% Set rotor time constant scale.
NO
bA.31
Regeneration
inductance
scale
80%
70 to 100% Set regeneration inductance scale.
NO
bA.32
Q-axis
inductance
scale
100%
50 to 100%
Adjust the inductance scale of the reactive
energy axis, Q, for the synchronous motors
permanant magnet motor control.
Note:
Visible parameter if dr.9 = PM Sensor-
less
NO
[3] These parameters will only be displayed if dr.9 is set to 4 (S-less1).
(*) This value depends on the motor setting.
Содержание SD 300 Series
Страница 1: ...SD300 GETTING STARTED MANUAL LOW VOLTAGE VARIABLE SPEED DRIVE ...
Страница 2: ......
Страница 3: ...Variable Speed Drive Getting Started Manual Edition February 2019 SD30IM01GI Rev G ...
Страница 159: ...POWER ELECTRONICS SD300 DESCRIPTION OF PROGRAMMING PARAMETERS 157 Power off delay ...
Страница 174: ...SD300 POWER ELECTRONICS 172 DESCRIPTION OF PROGRAMMING PARAMETERS TI configuration ...
Страница 352: ......
Страница 353: ......
Страница 354: ...24H TECHNICAL ASSISTANCE 365 DAYS A YEAR FIND YOUR NEAREST DELEGATION POWER ELECTRONICS COM CONTACT ...