112
DESCRIPTION OF PROGRAMMING PARAMETERS
Screen Description Default
value
Range
Function
Set
on
RUN
dr.19
Start
frequency
0.50Hz 0.01 to
10.00Hz
Set the start frequency. A start frequency is a
frequency at which the drive starts voltage
output. The drive does not produce output
voltage while the frequency reference is lower
than the set frequency. However, if a
deceleration stop is made while operating
above the start frequency, output voltage will
continue until the operation frequency reaches
a full-stop (0Hz).
NO
dr.20
Max speed
limit
60.00Hz
40.00 to
400.00
Hz
Set upper and lower frequency limits. All
frequency selections are restricted to
frequencies from within the upper and lower
limits.
This restriction also applies when you in input a
frequency reference using the keypad.
NO
Hz/Rpm
Display
Hz
Hz
Rpm
Change the units used to display the
operational speed of the drive by setting to 0
(Hz) or 1 (Rpm). This function is only available
in the removable display.
YES
dr.80
Select range
Run
Freq.
0 to 17
Select ranges displayed by the drive at power
input.
OPT. DESCR.
OPT. DESCR.
0
Run Freq.
9
Motor RPM
1
Accel. Time 10
DC Voltage
2
Decel. Time 11
User Sel. 1
3
Cmd Source 12
Out of Order
4
Ref. Source 13
Sel. Run Dir.
5
MultiStep 1
14
Oupt. Curr. 2
6
MultiStep 2
15
Motor2 RPM
7
MultiStep 3
16
DC Voltage2
8
Oupt. Curr.
17
User Sel. 2
YES
[1] Displayed when an LCD keypad is in use.
Содержание SD 300 Series
Страница 1: ...SD300 GETTING STARTED MANUAL LOW VOLTAGE VARIABLE SPEED DRIVE ...
Страница 2: ......
Страница 3: ...Variable Speed Drive Getting Started Manual Edition February 2019 SD30IM01GI Rev G ...
Страница 159: ...POWER ELECTRONICS SD300 DESCRIPTION OF PROGRAMMING PARAMETERS 157 Power off delay ...
Страница 174: ...SD300 POWER ELECTRONICS 172 DESCRIPTION OF PROGRAMMING PARAMETERS TI configuration ...
Страница 352: ......
Страница 353: ......
Страница 354: ...24H TECHNICAL ASSISTANCE 365 DAYS A YEAR FIND YOUR NEAREST DELEGATION POWER ELECTRONICS COM CONTACT ...