COMMONLY USED CONFIGURATIONS
17.
COMMONLY USED
CONFIGURATIONS
NOTICE
The following instructions are based on the assumption that all parameters are set
to the factory default values. Results may be different if parameter values have
been modified. In this case, set all parameters back to their default value and follow
the instructions.
Start/Stop command and speed setting from
keyboard
Parameter configuration
Parameter Default
value
Description
Set value
0.00
0.00Hz Frequency reference
x.xxHz (Set the frequency reference).
ACC
20.0 seg Acceleration time
10.0 sec
dEC
30.0 seg Deceleration time
10.0 sec
drv
1
Start/Stop control
0:
Start/Stop from keyboard.
frq
0
Frequency setting
mode
0:
Reference will be introduced from keyboard.
Ad.8
0
Stop mode
0:
Stop with deceleration ramp.
1:
DC brake to stop.
2:
Free run to stop.
4:
Regenerative brake to stop.
Ad.10
0
Start after low voltage.
0:
NO (Drive does not start after power loss).
1:
YES (Drive starts after power loss).
Ad.24
0
Use frequency limit
0:
NO (Limits are set by maximum frequency and
start frequency).
1:
YES (Limits are set by the higher and lower
frequency limits).
Ad.25
0.50Hz Frequency lower limit
0.00Hz
17
Содержание SD 300 Series
Страница 1: ...SD300 GETTING STARTED MANUAL LOW VOLTAGE VARIABLE SPEED DRIVE ...
Страница 2: ......
Страница 3: ...Variable Speed Drive Getting Started Manual Edition February 2019 SD30IM01GI Rev G ...
Страница 159: ...POWER ELECTRONICS SD300 DESCRIPTION OF PROGRAMMING PARAMETERS 157 Power off delay ...
Страница 174: ...SD300 POWER ELECTRONICS 172 DESCRIPTION OF PROGRAMMING PARAMETERS TI configuration ...
Страница 352: ......
Страница 353: ......
Страница 354: ...24H TECHNICAL ASSISTANCE 365 DAYS A YEAR FIND YOUR NEAREST DELEGATION POWER ELECTRONICS COM CONTACT ...