MODBUS COMMUNICATION
Modbus Address
Parameter
Scale Units Values
Decimal Hexadecimal
40817
0h0331
Latch type trip 2
information
-
-
Bit 0: MC Fail trip
Bit 2: PTC trip
Bit 3: Fan trip
Bit 5: Error while writing
parameter
Bit 6: Pre PID trip
Bit 7: External card contact fault
Bit 8: External brake trip
Bit 9: No motor trip
Bit 10: External card fault
40818
0h0332
Level type trip
information
-
-
Bit 0: Free run fault
Bit 1: Low voltage
Bit 2: Lost command
Bit 3: Display lost command
Bit 4: Safety A
Bit 5: Safety B
40819
0h0333
HW diagnosis trip
information
-
-
Bit 0: ADC error
Bit 1: EEPROM error
Bit 2: Watchdog1
Bit 3: Watchdog 2
Bit 5: Full queue
40820
0h0334
Warning information
-
-
Bit 0: Overload
Bit 1: Underload
Bit 2: Drive overload
Bit 3: Lost command
Bit 4: Fan running
Bit 5: DB
Bit 6: Wrong encoder
installation
Bit 7: Encoder disconnection
Bit 8: Keypad lost
Bit 9: Auto tuning failed
40832
0h0340
Days ON
0
Days
Total number of days the drive
has been powered on.
40833
0h0341
Minutes ON
0
Minutes
Total number of minutes the
drive has been powered on,
excluding the total number of
days.
40834
0h0342
Days on run
0
Days
Total number of days the drive
has been driving the motor.
Содержание SD 300 Series
Страница 1: ...SD300 GETTING STARTED MANUAL LOW VOLTAGE VARIABLE SPEED DRIVE ...
Страница 2: ......
Страница 3: ...Variable Speed Drive Getting Started Manual Edition February 2019 SD30IM01GI Rev G ...
Страница 159: ...POWER ELECTRONICS SD300 DESCRIPTION OF PROGRAMMING PARAMETERS 157 Power off delay ...
Страница 174: ...SD300 POWER ELECTRONICS 172 DESCRIPTION OF PROGRAMMING PARAMETERS TI configuration ...
Страница 352: ......
Страница 353: ......
Страница 354: ...24H TECHNICAL ASSISTANCE 365 DAYS A YEAR FIND YOUR NEAREST DELEGATION POWER ELECTRONICS COM CONTACT ...