POWER ELECTRONICS
SD300
DESCRIPTION OF PROGRAMMING PARAMETERS
189
Screen Description
Default
value
Range
Function
Set on
RUN
AP.20
Select PID
regulator
source
MREF
0 to 11
Select the source to introduce the PID
regulator set point:
OPT. DESCR. FUNCTION
0
MREF
PID set point introduced
from keypad.
1
V1
PID set point introduced by
the voltage analog input 1.
3
V2
PID set point introduced by
the voltage analog input 2.
4
I2
PID set point introduced by
the current analog input 2.
5
MODB
US
PID set point introduced
through
the
Modbus
communication protocol.
7
COMM
S
PID set point introduced
through any of the optional
communication boards.
8
PLC
PID set point introduced
through PLC.
11
PULSE
Reference signal through
the pulse input.
Note:
In case an unavailable option is
selected, the parameter will return to its
previous value.
NO
[32] Displayed when AP.1 is set to 2 (Proc PID).