POWER ELECTRONICS
SD300
POWER CONNECTIONS
65
Environment definition
The two environments are divided in four categories C1 to C4 that are
summarized in the following table.
FIRST ENVIRONMENT
SECOND ENVIRONMENT
C1
C2
C3
C4
Restricted Installation
[1]
NO
YES
YES
YES
[2]
Notes:
[1] “Restricted Installation” means that the installation and commissioning must be
carried out by specialist personnel.
[2] C4 Category applies only for complex systems or when ratings are equal or above
to 1000 V or 400 A wich are unable to comply with the limits of C3 Category. In these
cases, C4 Category can be achieved by adjusting the equipment in situ and applying
the EMC recommendations.
SD300 compliance
SD300 variable speed drives with Extended EMC have been designed for
the industrial use (Second Environment). In the case of the Standard EMC
equipment, an external filter must be installed to meet C3. The correct
installation following the recommendations within this manual, permit to
achieve compliance with C3 category defined in IEC/EN 61800-3.
Optionally, the SD300 drive with non-floating earth can be installed in
residential areas (First Environment) by employing optional RFI filters that
permit to achieve the C2 category.
The SD300 is not a retail unit. It is neither a plug in device nor a movable
device and it is intended to be installed and commissioned by qualified
personnel. However, C1 category will not be required.
The SD300 with floating earth configuration can be installed in industrial
(Second Environment) IT grids. Equipment with Extended EMC comply
with C3 (Second Environment). In the case of the Standard EMC
equipment, an external filter must be installed to meet C3.
Содержание SD 300 Series
Страница 1: ...SD300 GETTING STARTED MANUAL LOW VOLTAGE VARIABLE SPEED DRIVE ...
Страница 2: ......
Страница 3: ...Variable Speed Drive Getting Started Manual Edition February 2019 SD30IM01GI Rev G ...
Страница 159: ...POWER ELECTRONICS SD300 DESCRIPTION OF PROGRAMMING PARAMETERS 157 Power off delay ...
Страница 174: ...SD300 POWER ELECTRONICS 172 DESCRIPTION OF PROGRAMMING PARAMETERS TI configuration ...
Страница 352: ......
Страница 353: ......
Страница 354: ...24H TECHNICAL ASSISTANCE 365 DAYS A YEAR FIND YOUR NEAREST DELEGATION POWER ELECTRONICS COM CONTACT ...