DESCRIPTION OF PROGRAMMING PARAMETERS
Cn.36
Initial pole
position
estimation
interval
20ms 1
–
100ms
It allows adjusting the time interval between
retries to estimate the initial position of the
pole in a permanent magnet synchronous
motor (PM).
Note:
Visible parameter if dr.9 = PM
Sensor-less
NO
Cn.37
Initial pole
position
estimation
pulse current
(%)
15%
10
–
100%
It allows adjusting the value of the current
pulse in the estimation of the initial position
of the pole in a permanent magnet
synchronous motor (PM).
Note:
Visible parameter if dr.9 = PM
Sensor-less
NO
Cn.38
Initial pole
position
estimation
pulse voltage
(%)
500%
100
–
4000
It allows adjusting the value of the voltage
pulse in the estimation of the initial position
of the pole in a permanent magnet
synchronous motor (PM).
Note:
Visible parameter if dr.9 = PM
Sensor-less
NO
Cn.39
PM dead-time
range (%)
100.0%
50.0
–
200.0%
Sets the output compensation values during
the operation of a permanent magnet
synchronous motor in sensorless vector
control mode. If the motor does not run at
low speeds, at 5%, or less, of the rated
motor speed, increase the values in 10%
increments. Decrease the values by 10%
decrements if a clanking noise occurs at
motor startup and motor stop.
Note:
Visible parameter if dr.9 = PM
Sensor-less
NO
Cn.40
PM dead-time
voltage (%)
100.0%
50.0
–
200.0%
Cn.41
PM speed
estimator
proportional
gain
100
0
–
32000
Establish the values of the gain of the speed
estimator during the operation of a
permanent magnet synchronous motor in
sensorless vector control mode. If there is a
fault or the motor vibrates at low speed,
decrease this parameter by 10%
decrements until the motor runs correctly.
Note:
Visible parameter if dr.9 = PM
Sensor-less
NO
Содержание SD 300 Series
Страница 1: ...SD300 GETTING STARTED MANUAL LOW VOLTAGE VARIABLE SPEED DRIVE ...
Страница 2: ......
Страница 3: ...Variable Speed Drive Getting Started Manual Edition February 2019 SD30IM01GI Rev G ...
Страница 159: ...POWER ELECTRONICS SD300 DESCRIPTION OF PROGRAMMING PARAMETERS 157 Power off delay ...
Страница 174: ...SD300 POWER ELECTRONICS 172 DESCRIPTION OF PROGRAMMING PARAMETERS TI configuration ...
Страница 352: ......
Страница 353: ......
Страница 354: ...24H TECHNICAL ASSISTANCE 365 DAYS A YEAR FIND YOUR NEAREST DELEGATION POWER ELECTRONICS COM CONTACT ...