POWER ELECTRONICS
SD300
DESCRIPTION OF PROGRAMMING PARAMETERS
167
Screen Description Default
value
Range
Function
Set
on
RUN
In.70
Digital input 6
MultVel-
M
0 to 54
Note:
Comes from the previous page.
OPT. DESCR. FUNCTION
25 XCEL
Stop
Sets the digital input to
stop
acceleration
or
deceleration. See
Figure
Inputs configuration for
acceleration
/
deceleration
26 2ndMotor
Set the digital input as
2nd motor operation,
which is used when a
single drive switch
operates two motors.
34 Pre-Excit
Enable the motor pre-
excitation activation,
before start. The user can
adjust this functionality in
parameters Ad.7, Ad.1
and Ad.13.
38 TimerIN
Set the function for the
temporized digital output.
If option 28 “Timer
-
Ou” is
selected in OU.31 or
OU.33, the digital output
will be enabled once the
time set in OU.56 has
elapsed. Once this digital
input is disabled, the
digital output will be
disabled once the time
set in OU.57 has elapsed.
Note
: Continues on the next page.
NO
Содержание SD 300 Series
Страница 1: ...SD300 GETTING STARTED MANUAL LOW VOLTAGE VARIABLE SPEED DRIVE ...
Страница 2: ......
Страница 3: ...Variable Speed Drive Getting Started Manual Edition February 2019 SD30IM01GI Rev G ...
Страница 159: ...POWER ELECTRONICS SD300 DESCRIPTION OF PROGRAMMING PARAMETERS 157 Power off delay ...
Страница 174: ...SD300 POWER ELECTRONICS 172 DESCRIPTION OF PROGRAMMING PARAMETERS TI configuration ...
Страница 352: ......
Страница 353: ......
Страница 354: ...24H TECHNICAL ASSISTANCE 365 DAYS A YEAR FIND YOUR NEAREST DELEGATION POWER ELECTRONICS COM CONTACT ...