SD300
POWER ELECTRONICS
168
DESCRIPTION OF PROGRAMMING PARAMETERS
Screen Description Default
value
Range
Function
Set
on
RUN
In.71
Digital input 7
Mult Vel-
A
0 to 54
Note
: Comes from the previous page.
OPT. DESCR. FUNCTION
40
disAux
Ref.
This digital input sets the
main
reference
+
alternative
reference
functionality. When drive
speed is controlled by the
main reference source, if
this input is enabled, the
speed reference will be
calculated according to
parameter ba.2.
46
INCH(+) Enable the direct starting
fix speed reference to the
one set in parameter dr.11.
47
INCH(-)
49
XCEL-H
Bit 2 for alternative
acceleration ramps. Allows
the selection of the multiple
preconfigured
acceleration/deceleration
ramps. See bA.70 to 83.
50
PLC
Enables the user to
implement
simple
sequences using various
function blocks.
51
FireMode
The drive runs in Fire
mode when Ad.80 is set to
2 and the multifunction
terminal
(In
65-71)
configured for Fire mode is
turned on.
52
KEB1Sel
For
kinetic
energy
buffering operation, select
the multifunction terminal,
set it to ‘KEB1Sel’ and
enable the digital input.
Note
: Continues on the next page.
Содержание SD 300 Series
Страница 1: ...SD300 GETTING STARTED MANUAL LOW VOLTAGE VARIABLE SPEED DRIVE ...
Страница 2: ......
Страница 3: ...Variable Speed Drive Getting Started Manual Edition February 2019 SD30IM01GI Rev G ...
Страница 159: ...POWER ELECTRONICS SD300 DESCRIPTION OF PROGRAMMING PARAMETERS 157 Power off delay ...
Страница 174: ...SD300 POWER ELECTRONICS 172 DESCRIPTION OF PROGRAMMING PARAMETERS TI configuration ...
Страница 352: ......
Страница 353: ......
Страница 354: ...24H TECHNICAL ASSISTANCE 365 DAYS A YEAR FIND YOUR NEAREST DELEGATION POWER ELECTRONICS COM CONTACT ...