POWER ELECTRONICS
SD300
DESCRIPTION OF PROGRAMMING PARAMETERS
185
Screen Description
Default
value
Range
Function
Set on
RUN
CM.50
Number of
input
parameters
2
0 to 8
Configure a group of addresses to
read several input parameters at once.
The user must set the number of
parameters and then configure them in
CM.51-58.
YES
CM.51
[30]
Input
communication
addresses 1 to
8
40006
0 to 65535
Define the input parameter group for
data transmission, so that addresses
configured in CM.51-58 ca be used to
send several parameters at once in the
same communications frame.
The size of the group is set in CM.50
NO
CM.52
40007
NO
CM.53
40001
NO
CM.54
40001
NO
CM.55
40001
NO
CM.56
40001
NO
CM.57
40001
NO
CM.58
40001
NO
CM.68
Field bus data
swap
NO
NO
YES
Swap the most significant byte with the
least significant byte in order to adapt
to the PLC configuration.
NO
CM.70
Communication
multifunction
input 1 to 7
None
0 to 54
Multi-function inputs can be controlled
by using the communication address
40902. Configure parameters CM.70-
77 and then set the corresponding bit
in address 40803 for them to operate.
These inputs operate independently
from those set in In.65-71.
YES
CM.71
None
YES
[30] Only parameters corresponding to the value set in CM.50 will be shown (E.g., if
CM.50 = 2, parameters CM.51 and CM.52 will be shown).
Содержание SD 300 Series
Страница 1: ...SD300 GETTING STARTED MANUAL LOW VOLTAGE VARIABLE SPEED DRIVE ...
Страница 2: ......
Страница 3: ...Variable Speed Drive Getting Started Manual Edition February 2019 SD30IM01GI Rev G ...
Страница 159: ...POWER ELECTRONICS SD300 DESCRIPTION OF PROGRAMMING PARAMETERS 157 Power off delay ...
Страница 174: ...SD300 POWER ELECTRONICS 172 DESCRIPTION OF PROGRAMMING PARAMETERS TI configuration ...
Страница 352: ......
Страница 353: ......
Страница 354: ...24H TECHNICAL ASSISTANCE 365 DAYS A YEAR FIND YOUR NEAREST DELEGATION POWER ELECTRONICS COM CONTACT ...