POWER ELECTRONICS
SD300
DESCRIPTION OF PROGRAMMING PARAMETERS
153
Screen Description
Default
value
Range
Function
Set on
RUN
Cn.72
[20]
Speed search
mode current
150%
80 to
200%
Allows controlling the current during the
speed search in percentage in relation with
the motor rated current.
YES
Cn.73
[21]
Speed search
mode prop.
gain
Depends
on the
value of
Cn.70
0 to 9999
Allows setting the proportional gain for the
speed search.
Note:
The default value of this parameter
depends on Cn.70:
Flying Start1
➔
100
Flying Start2
➔
600
YES
Cn.74
Speed search
mode integral
gain
0 to 9999
Allows setting the proportional gain for the
speed search.
Note:
The default value of this parameter
depends on Cn.70:
Flying Start1
➔
200
Flying Start2
➔
1000
YES
Cn.75
Speed search
delay
1.0s
0.0 to
60.0s
Allows locking the output during an
established time before proceeding with the
speed search.
NO
Cn.76
Speed
estimator gain
100%
50 to
150% Speed search estimator gain.
YES
Cn.77
KEB Select
No
0 to 2
When the input power supply is
disconnected, the drive DC link voltage
decreases and a low voltage trip occurs
blocking the output. A kinetic energy
buffering operation uses regenerative
energy generated by the motor during the
blackout to maintain the DC link voltage.
This extends the time for a low voltage trip
to occur after a sudden power interruption.
This parameter allows selecting the kinetic
energy buffering operation. If 1 or 2 is
selected, it controls the drive output
frequency and charges the DC link (drive
DC part) with energy generated from the
motor.
Note
: Continues on the next page.
NO
[20] Displayed when any of the bits in Cn.71 bits are set to 1 and Cn.70 is set to 0.
[21] Displayed when any of the bits in Cn.71 bits are set to 1.
Содержание SD 300 Series
Страница 1: ...SD300 GETTING STARTED MANUAL LOW VOLTAGE VARIABLE SPEED DRIVE ...
Страница 2: ......
Страница 3: ...Variable Speed Drive Getting Started Manual Edition February 2019 SD30IM01GI Rev G ...
Страница 159: ...POWER ELECTRONICS SD300 DESCRIPTION OF PROGRAMMING PARAMETERS 157 Power off delay ...
Страница 174: ...SD300 POWER ELECTRONICS 172 DESCRIPTION OF PROGRAMMING PARAMETERS TI configuration ...
Страница 352: ......
Страница 353: ......
Страница 354: ...24H TECHNICAL ASSISTANCE 365 DAYS A YEAR FIND YOUR NEAREST DELEGATION POWER ELECTRONICS COM CONTACT ...