DESCRIPTION OF PROGRAMMING PARAMETERS
137
Screen Description Default
value
Range
Function
Set
on
RUN
Ad.71
[15]
Safe operation
stop
Free-
Run
Free-
Run
Q-Stop
Q-Stop
Res
Set the operation of the drive when the multi-
function input terminal in safe operation
mode is off.
OPT. DESCR. FUNCTION
0
Free-
Run
Blocks the drive output
when the multifunction
terminal is off.
1
Q-Stop
If the digital input
configured
as
’13
RUNEnable’ is disabled
when the drive is
operating,
the
drive
decelerates according to
the ramp defined in
parameter Ad.72. To
establish again the start
command, the input has
to be enabled while the
drive is stopped.
2
Q-Stop
Res
If the digital input
con
figured
as
‘13
RUNEnable’ is disabled
when the drive is
operating,
the
drive
decelerates according to
the ramp defined in
parameter Ad.72. If once
the permission digital
input is reset the start
command is present, the
drive will start normally.
Figure Safe operation stop
illustrates the
drive stop mode depending on the chosen
option.
NO
Ad.72
Q-Stop Time
5.0s
0.0 to
600.0s
Set the deceleration time when Ad.71 is set
to 1 (Q-Stop) or 2 (Q-Stop Res).
YES
[15] These parameters will only be displayed if Ad.70 is set to 1 (DI DEPENDENT).
Содержание SD 300 Series
Страница 1: ...SD300 GETTING STARTED MANUAL LOW VOLTAGE VARIABLE SPEED DRIVE ...
Страница 2: ......
Страница 3: ...Variable Speed Drive Getting Started Manual Edition February 2019 SD30IM01GI Rev G ...
Страница 159: ...POWER ELECTRONICS SD300 DESCRIPTION OF PROGRAMMING PARAMETERS 157 Power off delay ...
Страница 174: ...SD300 POWER ELECTRONICS 172 DESCRIPTION OF PROGRAMMING PARAMETERS TI configuration ...
Страница 352: ......
Страница 353: ......
Страница 354: ...24H TECHNICAL ASSISTANCE 365 DAYS A YEAR FIND YOUR NEAREST DELEGATION POWER ELECTRONICS COM CONTACT ...