POWER ELECTRONICS
SD300
COMMONLY USED CONFIGURATIONS
305
Parameter
Default
value
Description
Set value
dr.18
60.00Hz Motor frequency
50.00Hz
dr.19
0.50Hz Start frequency
0.10Hz
dr.20
60.00Hz Max speed limit
50.00Hz
dr.93
0
Parameter initialization
1:
Set parameters back to their factory value (only
if required).
dr.97
2.x
Software version
-
Cn.4
3kHz Modulation frequency
5kHz
In.65
1
Digital input 1
1:
Forward start command
In.70
8
Digital input 6
17:
UP
In.71
9
Digital input 7
18:
DOWN
(*) This value depends on the motor setting.
When the forward start command is sent (common CM), the drive will start
and maintain speed at 0Hz. When P6 pushbutton is pressed, the speed
will increase up to the minimum speed Ad.25, or to the speed stored in
memory if Ad.65=Y
Connection scheme
Terminals CM/P1: Run command (NO state).
Terminals CM/P6: Up push button (NO state).
Terminals CM/P7: Down push button (NO state).