POWER ELECTRONICS
SD300
DESCRIPTION OF PROGRAMMING PARAMETERS
141
Group 4: Control Functions
→
Cn
Screen Description
Default
value
Range
Function
Set on
RUN
Cn.4
Modulation
frequency
3.0kHz
-
Adjust motor operational noise by varying
the commutation frequency in the motor
output stage
If the frequency is set high, it reduces
operational noise from the motor, and if it is
set low, the operational noise from the motor
increases.
Default value and range for this parameter
depend on the load rate:
Normal load
: 2kHz (Max 5kHz).
Heavy load
: 3kHz (Max 15kHz).
NO
Cn.5
Modulation
mode
Normal
PWM
0 to 1
Change the modulation to reduce the heat
loss and leakage current from the drive:
OPT. DESCR. FUNCTION
0
Normal
PWM
No changes to load rate.
1
Low
Leakage
PWM
Reduces heat loss and
leakage
current
compared to Normal
PWM, but the motor noise
increases.
NO
Cn.9
Pre-excitation
time
1.00s
0.00 to
60.00s
Set the initial excitation time. Pre-excitation
is used to start the operation after
performing excitation up to the motor’s rated
flux.
NO
Содержание SD 300 Series
Страница 1: ...SD300 GETTING STARTED MANUAL LOW VOLTAGE VARIABLE SPEED DRIVE ...
Страница 2: ......
Страница 3: ...Variable Speed Drive Getting Started Manual Edition February 2019 SD30IM01GI Rev G ...
Страница 159: ...POWER ELECTRONICS SD300 DESCRIPTION OF PROGRAMMING PARAMETERS 157 Power off delay ...
Страница 174: ...SD300 POWER ELECTRONICS 172 DESCRIPTION OF PROGRAMMING PARAMETERS TI configuration ...
Страница 352: ......
Страница 353: ......
Страница 354: ...24H TECHNICAL ASSISTANCE 365 DAYS A YEAR FIND YOUR NEAREST DELEGATION POWER ELECTRONICS COM CONTACT ...