POWER ELECTRONICS
SD300
COMMONLY USED CONFIGURATIONS
299
Parameter
Default
value
Description
Set value
dr.15
0
Torque boost
0:
Manual torque (Both directions can be
configured separately, in dr.16
➔
‘Start torque in
forward direct
ion’ and in dr.17
➔
‘Start torque in
reverse direction’).
1 and 2:
The drive automatically calculates the
voltage to apply at the start using the motor
parameters.
dr.18
60.00Hz Motor frequency
50.00Hz
dr.19
0.50Hz Start frequency
0.10Hz
dr.20
60.00Hz Max speed limit
50.00Hz
dr.93
0
Parameter initialization
1:
Set parameters back to their factory value (only
if required)
dr.97
2.x
Software version
-
Cn.4
3kHz Modulation frequency 5kHz
In.65
1
Digital input 1
1:
Forward start command
In.69
7
Digital input 5
7:
Low Speed (Low bit).
In.70
8
Digital input 6
8:
Medium Speed (Medium bit).
In.71
9
Digital input 7
9:
High Speed (High bit).
bA.53
40.00Hz Multi-Reference4
45.00Hz (multiple speed 4).
bA.54
50.00Hz Multi-Reference5
50.00Hz (multiple speed 5).
bA.55
60.00Hz Multi-Reference6
47.00Hz (multiple speed 6).
bA.56
60.00Hz Multi-Reference7
42.00Hz (multiple speed 7).
Depending on the state of inputs P5, P6 y P7, the different configured
frequencies can be selected:
Содержание SD 300 Series
Страница 1: ...SD300 GETTING STARTED MANUAL LOW VOLTAGE VARIABLE SPEED DRIVE ...
Страница 2: ......
Страница 3: ...Variable Speed Drive Getting Started Manual Edition February 2019 SD30IM01GI Rev G ...
Страница 159: ...POWER ELECTRONICS SD300 DESCRIPTION OF PROGRAMMING PARAMETERS 157 Power off delay ...
Страница 174: ...SD300 POWER ELECTRONICS 172 DESCRIPTION OF PROGRAMMING PARAMETERS TI configuration ...
Страница 352: ......
Страница 353: ......
Страница 354: ...24H TECHNICAL ASSISTANCE 365 DAYS A YEAR FIND YOUR NEAREST DELEGATION POWER ELECTRONICS COM CONTACT ...