SD300
POWER ELECTRONICS
196
DESCRIPTION OF PROGRAMMING PARAMETERS
Screen Description
Default
value
Range
Function
Set on
RUN
Pr.6
Ripple voltage
15V
1 to
100V
Set the DC Bus ripple voltage that must be
exceeded to get a phase loss phase input
fault when Pr.5 is set as “INPUT” or “ALL”.
This value is set following customer’s
requirements.
NO
Pr.7
Fault
deceleration
time
3.0s
0.0 to
600.0s Deceleration time at fault trip.
YES
Pr.8
Start after
restart
N
N
S
Parameters Pr.9 and Pr.10 only operate
when Pr.8 is set to 1(Yes).
The number of attempts to try the auto
restart is set at Pr.9.
If a fault trip occurs during operation, the
drive automatically restarts after the set time
programmed at Pr.10.
At each restart, the drive counts the number
of tries and subtracts it from the number set
at Pr.9 until the retry number count reaches
0. After an auto restart, if a fault trip does not
occur within 60 secs, it will increase the
restart count number. The maximum count
number is limited by Pr.10.
YES
Pr.9
Retry attempts
number
0
0 to 10
YES
Pr.10
[33]
Retry delay
1.0s
0.0 to
60.0s
YES
[33] Displayed when Pr.9 is higher than zero.
Содержание SD 300 Series
Страница 1: ...SD300 GETTING STARTED MANUAL LOW VOLTAGE VARIABLE SPEED DRIVE ...
Страница 2: ......
Страница 3: ...Variable Speed Drive Getting Started Manual Edition February 2019 SD30IM01GI Rev G ...
Страница 159: ...POWER ELECTRONICS SD300 DESCRIPTION OF PROGRAMMING PARAMETERS 157 Power off delay ...
Страница 174: ...SD300 POWER ELECTRONICS 172 DESCRIPTION OF PROGRAMMING PARAMETERS TI configuration ...
Страница 352: ......
Страница 353: ......
Страница 354: ...24H TECHNICAL ASSISTANCE 365 DAYS A YEAR FIND YOUR NEAREST DELEGATION POWER ELECTRONICS COM CONTACT ...