POWER ELECTRONICS
SD300
DESCRIPTION OF PROGRAMMING PARAMETERS
197
Screen Description
Default
value
Range
Function
Set on
RUN
Pr.12
Response in
case of a
speed
reference loss
None
0 to 5
Set the action to be taken if the drive loses
a speed reference:
OPT. DESCR. FUNCTION
0
None Protection is disabled.
1
Free-
Run
The drive cuts the output
voltage and allows the
motor free run.
2
Dec
The motor decelerates and
then stops at the time set
at Pr.7.
3
Hold
Input
The drive will keep
operating to the input
value,
mean
value
obtained from the last 10
seconds until the moment
the reference lo s has been
detected.
4
Hold
Output
The drive will keep
operating to the input
value,
mean
value
obtained from the last 10
seconds until the moment
the reference loss has
been detected.
5
Lost
Preset
The drive operates to the
frequency
defined
in
parameter Pr.14.
Caution
: Users should ensure that
disabling this protection does not
compromise the operation of the equipment
YES
Содержание SD 300 Series
Страница 1: ...SD300 GETTING STARTED MANUAL LOW VOLTAGE VARIABLE SPEED DRIVE ...
Страница 2: ......
Страница 3: ...Variable Speed Drive Getting Started Manual Edition February 2019 SD30IM01GI Rev G ...
Страница 159: ...POWER ELECTRONICS SD300 DESCRIPTION OF PROGRAMMING PARAMETERS 157 Power off delay ...
Страница 174: ...SD300 POWER ELECTRONICS 172 DESCRIPTION OF PROGRAMMING PARAMETERS TI configuration ...
Страница 352: ......
Страница 353: ......
Страница 354: ...24H TECHNICAL ASSISTANCE 365 DAYS A YEAR FIND YOUR NEAREST DELEGATION POWER ELECTRONICS COM CONTACT ...