SD300
POWER ELECTRONICS
162
DESCRIPTION OF PROGRAMMING PARAMETERS
Screen Description Default
value
Range
Function
Set
on
RUN
In.65
Digital input 1 START
(+)
0 to 54
Digital Inputs configuration for individual use.
OPT. DESCR. FUNCTION
0 None
Not programmed entry.
1 START(+)
Send the start command
through an open contactor
(NO). The operation of the
Digital Input varies when
‘3 WIRE’ is
selected.
2 START(-)
Send the reverse start
command through an
open contactor (NO). The
operation of the Digital
Input varies when ‘3
WIRE’ is selected.
3 RESET
Send a ‘Reset’ comman
d
through digital inputs.
(NO)
4 EXTTRIP
Trigger an external fault to
stop the drive through
digital inputs (NO). Is
advisable to invert the
digital
input
logic
configured as Extreme
Fault and set it as contact
(NC). See parameter
In.87.
5 DISSTART
Stop the drive by
removing the motor output
power supply, forcing a
stop by inertia. (NO)
6 INCH1
Enable
the
speed
reference programmed in
dr.11. (NO)
Note
: Continues on the next page
NO
Содержание SD 300 Series
Страница 1: ...SD300 GETTING STARTED MANUAL LOW VOLTAGE VARIABLE SPEED DRIVE ...
Страница 2: ......
Страница 3: ...Variable Speed Drive Getting Started Manual Edition February 2019 SD30IM01GI Rev G ...
Страница 159: ...POWER ELECTRONICS SD300 DESCRIPTION OF PROGRAMMING PARAMETERS 157 Power off delay ...
Страница 174: ...SD300 POWER ELECTRONICS 172 DESCRIPTION OF PROGRAMMING PARAMETERS TI configuration ...
Страница 352: ......
Страница 353: ......
Страница 354: ...24H TECHNICAL ASSISTANCE 365 DAYS A YEAR FIND YOUR NEAREST DELEGATION POWER ELECTRONICS COM CONTACT ...