POWER ELECTRONICS
SD300
DESCRIPTION OF PROGRAMMING PARAMETERS
165
Screen Description Default
value
Range
Function
Set
on
RUN
In.68
Digital input 4 RESET 0 to 54
Note
: Comes from the previous page.
OPT. DESCR. FUNCTION
16
EXCHAN
GE
This option switches motor
power supply from the
drive with direct network
supply. To do this, digital
output options 17 ‘Line in’
and 18
‘Line Co’ are used.
While the digital input is
open, the digital output
configured as 17 ‘Line in’
remains active. Once this
digital input is closed, the
relay ‘Line in’ is disabled,
waits for 500ms and
enables ‘Line Co’. When
this digital input in
disable
d, ‘Line Co’ is
disabled, waits for 500ms,
enables ‘Line In’ and
performs a speed search
to synchronize with the
motor.
See
Figure
Multifunction
relay
configuration
.
17
UP
Assign the function to
increase
the
speed
reference through a button
(NO) to the digital input.
reference limits are those
set in dr group.
18
DOWN
Set digital input to
decrease
the
speed
reference by the use of a
button
(NO).
The
reference limits will be
those set on dr group
Note
: Continues on the next page.
YES
Содержание SD 300 Series
Страница 1: ...SD300 GETTING STARTED MANUAL LOW VOLTAGE VARIABLE SPEED DRIVE ...
Страница 2: ......
Страница 3: ...Variable Speed Drive Getting Started Manual Edition February 2019 SD30IM01GI Rev G ...
Страница 159: ...POWER ELECTRONICS SD300 DESCRIPTION OF PROGRAMMING PARAMETERS 157 Power off delay ...
Страница 174: ...SD300 POWER ELECTRONICS 172 DESCRIPTION OF PROGRAMMING PARAMETERS TI configuration ...
Страница 352: ......
Страница 353: ......
Страница 354: ...24H TECHNICAL ASSISTANCE 365 DAYS A YEAR FIND YOUR NEAREST DELEGATION POWER ELECTRONICS COM CONTACT ...