POWER ELECTRONICS
SD300
DESCRIPTION OF PROGRAMMING PARAMETERS
117
Screen Description Default
value
Range
Function
Set
on
RUN
The following table shows the calculation for
each option, where:
M: Main speed reference
G: Auxiliary reference gain (bA.3)
A: Auxiliary reference (bA.1)
OPT. CALCULATION FUNCTION
0
M+(G*A)
𝑀𝑎𝑖𝑛 𝑟𝑒𝑓.
+ (𝑏𝐴. 3 ∗ 𝑏𝐴. 1
∗ 𝐼𝑛. 1)
1
Mx(G*A)
𝑀𝑎𝑖𝑛 𝑟𝑒𝑓.
∗ (𝑏𝐴. 3 ∗ 𝑏𝐴. 1)
2
M/(G*A)
𝑀𝑎𝑖𝑛 𝑟𝑒𝑓.
/ (𝑏𝐴. 3 ∗ 𝑏𝐴. 1)
3
M+[M*(G*A)]
𝑀𝑎𝑖𝑛 𝑟𝑒𝑓.
+ {𝑀𝑎𝑖𝑛 𝑟𝑒𝑓.
∗ (𝑏𝐴. 3 ∗ 𝑏𝐴. 1)}
4
M+G*2(A-50%)
𝑀𝑎𝑖𝑛 𝑟𝑒𝑓.
+ 𝑏𝐴. 3 ∗ 2
∗ (𝑏𝐴. 1 − 50)
∗ 𝐼𝑛. 1
5
Mx[G*2(A-50%)
𝑀𝑎𝑖𝑛 𝑟𝑒𝑓.
∗ (𝑏𝐴. 3 ∗ 2
∗ (𝑏𝐴. 1 − 50))
6
M/[G*2(A-50%)]
𝑀𝑎𝑖𝑛 𝑟𝑒𝑓.
/(𝑏𝐴. 3 ∗ 2
∗ (𝑏𝐴. 1 − 50))
7
M+M*G*2(A-
50%)
𝑀𝑎𝑖𝑛 𝑟𝑒𝑓.
+ 𝑀𝑎𝑖𝑛 𝑟𝑒𝑓.
∗ 𝑏𝐴. 3 ∗ 2
∗ (𝑏𝐴. 1 − 50)
Auxiliary
reference
gain
1000%
-200.0 to
200.0%
Adjust a gain to the auxiliary reference
configured in parameter.
YES