POWER ELECTRONICS
SD300
DESCRIPTION OF PROGRAMMING PARAMETERS
105
Screen
Description
Default
value
Modbus Address
Function
DEC
HEX
Multi-step
speed
frequency 3
30.00Hz
47943
0h1F07
See group Basic Functions (bA),
parameter St3.
CUr
Output current
-
47944
0h1F08
These values depend on drive
characteristics.
rPM
Motor
revolutions
per minute
-
47945
0h1F09
dCL
Inverter
direct
current voltage
-
47946
0h1F0A
vOL
Inverter
output
voltage
-
47947
0h1F0B
LuT
Out of order signal
-
47948
0h1F0C
drC
Select
rotation
direction
-
47949
0h1F0D
Group 1: Drive
→
dr
Screen Description
Default
value
Range
Function
Set
on
RUN
Local speed
0.00Hz dr.19 to
dr.20
Set the motor speed value. Minimum value is
set in dr.19 and the maximum value in dr.20.
YES
dr.2
Local torque
0.0%
-180.0
to
180.0%
Set the torque value of the motor.
YES
Acceleration
ramp
20.0s
0.0 to
600.0s
Set the acceleration ramp 1, in seconds. This
ramp will be set according to the requirements
of each process.
YES
Deceleration
ramp
30.0s
0.0 to
600.0s
Set the deceleration ramp 1, in seconds. This
ramp will be set according to the requirements
of each process.
YES
[1] Displayed when an LCD keypad is in use.
Содержание SD 300 Series
Страница 1: ...SD300 GETTING STARTED MANUAL LOW VOLTAGE VARIABLE SPEED DRIVE ...
Страница 2: ......
Страница 3: ...Variable Speed Drive Getting Started Manual Edition February 2019 SD30IM01GI Rev G ...
Страница 159: ...POWER ELECTRONICS SD300 DESCRIPTION OF PROGRAMMING PARAMETERS 157 Power off delay ...
Страница 174: ...SD300 POWER ELECTRONICS 172 DESCRIPTION OF PROGRAMMING PARAMETERS TI configuration ...
Страница 352: ......
Страница 353: ......
Страница 354: ...24H TECHNICAL ASSISTANCE 365 DAYS A YEAR FIND YOUR NEAREST DELEGATION POWER ELECTRONICS COM CONTACT ...