- 77 -
Set
value
Function
Description
(
RJOG
)
6
Terminal UP
When the frequency is given by the external terminal, the
frequency is increased and decremented. The frequency source
is set to
When the digit is set, adjust the set frequency up and down.
7
Terminal DOWN
8
Freely stop
The inverter blocks the output, and the motor stop process is not
controlled by the inverter, This way with. The meaning of free
parking as described in P6-10 is the same.
9
Fault reset
(
RESET
)
Use the terminal to perform a fault reset function. With the same
function as the RESET key on the keyboard.
Use this function to enable remote fault reset.
10
Working stop
The drive decelerates, but all operating parameters are
memorized. Such as PLC parameters, wobble parameters,
PID parameters. When the terminal signal disappears, the
inverter returns to the running state before stopping.
11
External fault
normally open
input
When the signal is sent to the inverter, the inverter reports fault
FU15, and according to the fault protection action side (Refer to
function code P9-47 for details).
12
Multi-speed
terminal 1
Through the four terminals of the 16 states, to achieve 16
speed or 16 other instructions
The setting. See Table 1 for details.
13
Multi-speed
terminal 2
14
Multi-speed
terminal 3
15
Multi-speed
terminal 4
16
Acceleration/
deceleration time
selection terminal
1
Through the four terminals of the four states, to achieve four
kinds of acceleration and deceleration time selection, the
details
See Schedule 2
17
Acceleration/
deceleration time