- 92 -
Set
value
Function
Pulse or analog output 0.0% to 100.0% of the
corresponding function
settings
13
Motor speed
0
~
The maximum output frequency corresponds
to the speed
14
Output current
0.0A~1000.0A
15
output voltage
0.0V~1000.0V
16
Output torque (actual
value)
-2 times the motor rated torque~2 times the motor
rated torque
P5-09
HDP output max
frequency
Factory default
50.00kHz
Set range
0.01kHz
~
100.00kHz
When the HDO terminal is selected as a pulse output, the function code is used to select
the maximum frequency value of the output pulse.
The above function codes are generally used to correct the zero drift of the analog output
and the deviation of the output amplitude. It can also be used to customize the desired AO
output curve.
If the zero is denoted by "b", the gain is denoted by k, the actual output is denoted by Y,
and the standard output is denoted by X, then the actual output is: Y = kX + b.
Among them, AO1, AO2 zero partial coefficient of 100% corresponds to 10V (or 20mA),
the standard output is no zero bias and gain correction, the output 0V ~ 10V (or 0mA ~
20mA) corresponding to the amount of analog output.
For example, if the analog output content is the operating frequency, it is desirable to
output 8V when the frequency is 0 and 3V when the frequency is the maximum frequency.
The gain should be set to "-0.50" and the zero bias should be set to "80%".
P5-17
HDY
output the delay
time
Factory setting
0.0s
Set range
0.0s
~
3600.0s
P5-18
Relay 1 outputs the delay
time
Factory setting
0.0s
Set range
0.0s
~
3600.0s
Set the output terminal HDY, relay 1, relay 2, from the state change to the actual output to
produce changes in the delay time
P5-22
HDO Output terminal
valid status selection
Factory default
00000
P5-10
AO1 Zero partial
coefficient
Factory default
0.0%
Set range
-100.0%
~
+100.0%
P5-11
AO1 profits
Factory default
1.00
Set range
-10.00
~
+10.00