- 127 -
PC-47
Easy PLC paragraph 14
acceleration /
deceleration
Factory default
0
Set range
0
~
3
PC-48
Simple PLC fifteenth run
time
Factory default
0.0s
(
h
)
Set range
0.0s
(
h
)~
6553.5s
(
h
)
PC-49
Easy PLC paragraph 15
acceleration /
deceleration
Factory default
0
Set range
0
~
3
PC-50
Simple PLC run time
unit
Factory default
0
Set range
0
:
S
(
s
)
1
:
h
(
h
)
PC-51
Multi-step instruction 0
given mode
Factory default
0
Set range
0: Function code PC-00 reference 1: AI1 2: AI2
3: AI3 4: High speed pulse input 5: PID
6: Preset frequency (P0-08) is given, UP / DOWN can be
modified
This parameter determines the given channel for multi-step instruction 0.
In addition to the PC-00, there are a number of other options that allow you to toggle
between multiple short and other ways. In the multi-segment instructions as a frequency
source or simple PLC as a frequency source, can easily achieve the two frequency source
switching
Pd Group Communication parameters
Please refer to "communication protocol"
PP Group user password
PP-00 set any non-zero number, the password protection function to take effect. The next
time you enter the menu, you must enter the correct password, or cannot view and modify
the function parameters, please keep in mind the user password set. Set the PP-00 to 00000,
then clear the set user password, so that the password protection function is invalid.
A0 Group Torque control and qualification
A0-00
Speed / torque control
mode selection
Factory default
0
Set range
0: Speed control 1: Torque control
Used to select the inverter control mode: speed control or torque control.
DSI-200 multi-function digital S terminal, with two torque control related functions: torque
control disabled (function 29), speed control / torque control switch (function 46). The two
PP-00
User password Factory default
0
Set range
0
~
65535