- 133 -
Figure 6-31 Curve 4 and Curve 5 Schematic
Curve 4 and curve 5 should be noted that the minimum input voltage curve, the inflection
point 1 voltage, inflection point 2 voltage, the maximum voltage must be increased in turn.
AI curve selection P4-33, used to determine the analog input AI1 ~ AI3 how to choose from
5 curves.
A6-24
AI1 Set jump point
Factory default
0.0%
Set range
-100.0%
~
100.0%
A6-25
AI1 Set the jump range
Factory default
0.5%
Set range
0.0%
~
100.0%
A6-26
AI2 Set jump point
Factory default
0.0%
Set range
-100.0%
~
100.0%
A6-27
AI2 Set the jump range
Factory default
0.5%
Set range
0.0%
~
100.0%
The jump function means that when the analog quantity is set at the upper and lower range
of the jump point, the analog value corresponding to the set value is fixed to the value of the
jump point.
For example
:
The analog input AI1 voltage fluctuates above 5.00V, the fluctuation range is 4.90V ~ 5.10V,
the AI1 minimum input 0.00V corresponds to 0.0%, the maximum input 10.00V corresponds
to 100.%, then the detected AI1 correspondence is set at 49.0 % ~ 51.0% fluctuate.
Set the AI1 to set the jump point A6-24 to 50.0%, set AI1 to set the jump amplitude A6-25
to 1.0%, then the AI1 input, after the jump function processing, the AI1 input corresponding
to the fixed set to 50.0% AI1 is transformed into a stable input, eliminating the fluctuation.
d0 Group Monitor the parameter group
d0 parameter group is used to monitor the inverter running status information, the
customer can view through the panel to facilitate on-site debugging, you can also read the