- 17 -
Model
Empty open
(
MCCB
)
A
Recommend
Contactor
A
Recommended
input side
Main circuit
lead wire mm
2
Recommended
output side
main
Circuit wire
mm
2
Recommended
control circuit
Wire mm
2
DSI-200-2K2G3
16
10
2.5
2.5
1.0
DSI-200-
004G3/5K5P3
25
16
4.0
4.0
1.0
DSI-200-
5K5G3/7K5P3
32
25
4.0
4.0
1.0
3.2.2 Connect with peripheral devices