- 34 -
P3-13
Voltage source for V/F
separation
0: digital setting (P3-14)
1: AI1 (Note: J6 jumper)
2: AI2 3: AI3
4: High-speed pulse input
setting (S5)
5: multi-segment instructions
6: Simple PLC 7: PID
8: communication given
Note: 100.0% corresponds to the
motor rated voltage
0
☆
P3-14
Digital setting of voltage for
V/F
separation
0V
~
motor rated voltage
0V
☆
P3-15
Voltage rise time of V/F
separation
0.0s
~
1000.0s
Note: 0v to rated motor voltage
0.0s
☆
P3-16
Voltage decline time of V/F
separation
0.0s~1000.0s
Note: time of 0v to rated motor
voltage
0.0s
☆
P3-17
Stop mode selection for V/F
separation
0: Frequency and voltage
declining to 0 independently
1: Frequency declining after
voltage declines to 0
0
☆
P3-18
Current limit level
50~200%
150%
★
P3-19
Current limit selection
0
:
useless 1
:
useful
1
★
P3-20
Current limit gain
0~100
20
☆
P3-21
Compensation factor of
speed
multiplying current limit
level
50~200%
50%
★
P3-22
Voltage limit
650V~800.0V
770V
★
P3-23
Voltage limit selection
0
:
useless 1
:
useful
1
★
P3-24
Frequency gain for voltage
limit
0~100
30
☆
P3-25
Voltage gain for voltage
limit
0~100
30
☆