- 55 -
weakening area
A2-60
Regenerative power limit selection
0: Disabled
1: Enabled in whole process
2: Enabled at constant
speed
3: Enabled during
deceleration
0
☆
A2-61
Regenerative power upper limit
0.0% to 200.0%
Model
dependent
☆
A2-62
Motor 2 control mode
0 to 2
0
★
A2-63
Motor 2 acceleration/deceleration
time selection
0 to 4
0
☆
A2-64
Motor 2 torque boost
0.0%: Ineffective
0.1% to 30.0%
Model
dependent
☆
A2-66
Motor 2 oscillation suppression
gain
0 to 100
40
☆
Group A5: Control Optimization
A5-00
DPWM switchover frequency
upper limit
5.00 Hz to max. frequency
8.00 Hz
☆
A5-01
PWM modulation pattern
0, 1
0
☆
A5-02
Dead zone compensation mode
selection
0, 1
1
☆
A5-03
Random PWM depth
0 to 10
0
☆
A5-04
Over current fast prevention
0, 1
1
☆
A5-05
Voltage over modulation
coefficient
100% to 110%
105%
★
A5-06
Under voltage threshold
210 to 420 V
350 V
☆
A5-08
Dead-zone time adjustment
100% to 200%
150%
★
A5-09
Over voltage threshold
200.0 to 2500.0 V
Model
dependent
★
Para. No.
Para. Name
Setting Range
Default
Prop
erty
Group A6: AI Curve Setting
A6-00
AI curve 4 min. input
-10.00 V to A6-02
0.00 V
☆
A6-01
Corresponding percentage of AI
curve 4 min. input
-100.0% to 100.0%
0.0%
☆
A6-02
AI curve 4 inflexion 1 input
A6-00 to A6-04
3.00 V
☆
A6-03
Corresponding percentage of AI
curve 4 inflexion 1 input
-100.0% to 100.0%
30.0%
☆
A6-04
AI curve 4 inflexion 2 input
A6-02 to A6-06
6.00 V
☆
A6-05
Corresponding percentage of AI
curve 4 inflexion 2 input
-100.0% to 100.0%
60.0%
☆
A6-06
AI curve 4 max. input
A6-04 to 10.00 V
10.00 V
☆
A6-07
Corresponding percentage of AI
curve 4 max. input
-100.0% to 100.0%
100.0%
☆
A6-08
AI curve 5 min. input
-10.00 V to A6-10
-10.00 V
☆
A6-09
Corresponding percentage of AI
curve 5 min. input
-100.0% to 100.0%
-100.0%
☆