166
Pd-05 = 1: Select the standard Modbus protocol.
Pd-05 = 0: When reading a command, the number of bytes
returned by the slave is one byte greater than the standard Modbus
protocol. Refer to the "5 Communication Data Structure" section
of this protocol.
Pd-06
Communication read
current resolution
Factory default
0
Set range
0
:
0.01A
;
1
:
0.1A
Used to determine the output unit of the current value when the
communication reads the output current
Setting Range
Bit: MODBUS
0: Non-standard MODBUS
protocol
1: Standard MODBUS
protocol
Ten: Profibus-DP
0: PPO1 format