- 30 -
P0-27
The run command is tied to
the main frequency source
A command selection
:
Bit: Operation panel command
Bind frequency source selection
0: no binding
1: Digital setting frequency
2: AI1 (Note: J6 jumper)
3: AI2
4: AI3
5: High-speed pulse input setting
(S5)
6: multi-speed
7: Simple PLC
8: PID
9: communication given
Ten: Terminal Command Binding
Frequency Source Selection
Hundreds:
communication
command
binding
frequency
source selection
0000
☆
P0-28
Serial port comms. protocol
0
:
Modbus communication
0
☆
P1 Motor 1 Parameters
P1-00
Motor type selection
0: Ordinary asynchronous motor
1:Variable
frequency
asynchronous motor
0
★
P1-01
Rated motor power
0.1kW
~
1000.0kW
Model
dependent
★
P1-02
Rated motor voltage
1V
~
2000V
Model
dependent
★
P1-03
Rated motor current
0.01 to 655.35 A (AC drive
power ≤ 55 kW)
Model
dependent
★
P1-04
Rated motor frequency
0.01Hz
~
Max frequency
Model
dependent
★
P1-05
Rated motor speed
1rpm
~
65535rpm
Model
dependent
★
P1-06
Stator resistance
0.001Ω
~
65.535Ω
0.0001Ω
~
6.5535Ω
Auto-tuning
dependent
★
P1-07
Rotor resistance
0.001Ω
~
65.535Ω
Auto-tuning
dependent
★
P1-08
Leakage inductive reactance
0.01mH
~
655.35mH
Auto-tuning
dependent
★
Function
Code
Name
Set Range
default
Alteration