164
Group
Pd
Communication
Parameter
Description
This parameter is used to set transmission speed between host
computer and AC drive. Note that baud rate of host computer must
be the same as that of AC drive. Otherwise, communication shall
fail. The higher baud rate is, the faster communication will be.
Pd-01
Modbus Data
format
Factory default
0
Set range
0: No check <8,N,2>
1: Even parity check <8,E,1>
2: Odd parity check <8,O,1>
3: No check, data format <8,N,1>
Note that data format of host computer must be the same as that of
AC drive. Otherwise, communication shall fail.
Pd-02
Local address
Factory default
1
Set range
1~247
,
0 Broadcast address
This parameter is used to set address of AC drive. This address is
unique (except broadcast address), which is basis for point-to-
point communication between host computer and AC drive. When
Pd-00
Baud rate
Factory default
6005
Set range
Bit
:
MODBUS Baud rate
0
:
300BPS
1
:
600BPS
2
:
1200BPS
3
:
2400BPS
4
:
4800BPS
5
:
9600BPS
6
:
19200BPS
7
:
38400BPS
8
:
57600BPS
9
:
115200BPS