- 84 -
P4-00
S1
Terminal
function
choose
1
RUNNING
P4-01
S2
Terminal
function
choose
2
Forward and reverse
direction of operation.
P4-02
S3
Terminal
function
choose
3
Three - wire operation
control
Figure 6-11 Three - wire control mode 2
As shown in the figure above, the control mode is in the SB1 button closed state, press the
SB2 button inverter running, K disconnect the inverter forward, K closed inverter reverse;
SB1 button off instantaneous inverter shutdown. During normal startup and operation, the
SB1 button must be closed and the command of the SB2 button will take effect at the
closing action edge.
For setting the terminal UP / DOWN to adjust the set frequency, the speed of the frequency
change, that is, the amount of change per second.
P4-13
AI curve 1 min input
Factory
default
0.00V
Set range
0.00V
~
P4-15
P4-14
AI Curve 1 minimum input
corresponds to setting
Factory
default
0.0%
Set range
-100.00%
~
100.0%
P4-15
AI Curve 1 maximum input
Factory
default
10.00V
Set range
P4-13
~
10.00V
P4-16
AI Curve 1 maximum input
corresponds to setting
Factory
default
100.0%
Set range
-100.00%
~
100.0%
P4-17
AI1 Input filter time
Factory
default
0.10s
Set range
0.00s
~
10.00s
P4-12
Terminal UP/DOWN Frequency
change rate
Factory default
1.00Hz/s
Set range
0.01Hz/s
~
65.535Hz/s