- 107 -
P8-34
Zero current detection level
Factory
default
5.0%
Setting Range
0.0%
~
300.0%
(
rated motor current)
P8-35
Zero current detection delay
Factory
default
0.10s
Setting Range
0.00s
~
600.00s
When the output current of the inverter is less than or equal to the detection level of the
zero current and the delay time exceeds the zero current detection delay time, the multi-
function terminal HDY outputs the ON signal. Figure 6-21 is a schematic diagram of zero
current detection.
Figure 6-21 Zero current detection.
P8-36
Output over current threshold
Factory default
200.0%
Setting Range
0.0%
(
no detection)
;
0.1%
~
300.0%
(
rated motor current
)
P8-37
Output over current detection
delay
Factory default
0.00s
Setting Range
0.00s
~
600.00s
If the inverter output current is equal to or more than the value set in P8-36 and the delay
time exceeds the value set in P8-37, multi-function terminal HDY output on signal. Figure
6-22 Output current limit.