- 91 -
37
Lower frequency
arrival
(Shutdown also output)
When the operating frequency reaches the lower
limit frequency, the ON signal is output. The signal is
also ON in the shutdown state
38 Warning output
When the inverter fails, and the fault processing
mode for the continued operation, the inverter alarm
output.
39
Motor over
temperature alarm
When the motor temperature reaches P9-58 (motor
overheat pre-alarm threshold), the ON signal is
output. (Motor temperature can be viewed by d0-34)
40 The run time arrives
When the inverter starts running for more than the
time set by P8-53, the ON signal is output.
41 Fault output
Fault output (for freewheel failure and undervoltage
is not output)
P5-06
HDP Output function selection
(
Pulse
output terminal
)
Factory
default
0
P5-07
AO1 Output function selection
Factory
default
0
HDP terminal output pulse frequency range of 0.01 KHz ~ P5-09 (HDO output maximum
frequency), P5-09 can be set between 0.01 kHz ~ 100.00 kHz.
Analog output AO1 and AO2 output range of 0V ~ 10V, or 0mA ~ 20mA.
Pulse output or analog output range, and the corresponding function of the scaling
relationship as shown in the following table:
Set
value
Function
Pulse or analog output 0.0% to 100.0% of the
corresponding function
0
Working frequency
0
~
max output frequency
1
Set frequency
0
~
max output frequency
2
Output current
0
~
2 times motor rated current
3
Output torque
(
Absolute value
)
0
~
2 times rated Output torque
4
Output power
0
~
2 times rated power
5
Output voltage
0
~
1.2times AC drive output voltage
6
High speed pulse
input
0.01kHz
~
100.00kHz
7
AI1
0V
~
10V
8
AI2
0V
~
10V
(
or 0
~
20mA
)
9
AI3
0V
~
10V
10
Length
0
~
max set length
11
Number setting
0
~
max number
12
Communication
0.0%
~
100.0%