- 106 -
P8-28
Frequency detection value 2
(
FDT2
)
Factory default
50.00Hz
Setting Range
0.00Hz
~
max. frequency
P8-29
Frequency detection
hysteresis 2
Factory
default
5.0%
Setting Range
0.0%
~
100.0%
(
FDT2 electric level
)
The frequency detection function is exactly the same as the function of FDT1. Please refer
to the relevant instructions of FDT1 with the function code P8-19 and P8-20.
P8-30
Detection of frequency 1
Factory
default
50.00Hz
Setting
Range
0.00Hz
~
max. frequency
P8-31
Detection width of frequency
1
Factory
default
0.0%
Setting
Range
0.0%
~
100.0%
(
max. frequency
)
P8-32
Detection of frequency 2
Factory
default
50.00Hz
Setting
Range
0.00Hz
~
max. frequency
P8-33
Detection width of frequency
2
Factory
default
0.0%
Setting
Range
0.0%
~
100.0%
(
max. frequency
)
When the output frequency of the inverter is within positive and negative detection range
of frequency detection value, the multi-functional terminal DO outputs the ON signal.
DSI-200 provides two sets of random arrival frequency detection parameters, respectively
setting frequency value and frequency detection range. Figure 6-20 is a schematic diagram
of the delection of frequency function.
Figure 6-20 Delection of frequency arrive function.