76
to either the HR or DM area, and then restore by using TRANSFER DATA
the next time the Unit is powered up.
The following programming example shows word n+8 data moving to word
HR 00 and word n+9 data moving to word HR 01. If there is no origin, bit 11
of word n+5 (the no-origin flag) turns ON (goes to 1). As long as there is an
origin and the present position data is valid, the present position will be trans-
ferred.
0 CW
1 CCW
n+8
n+9
15 00
x10
3
x10
2
x10
1
x10
0
x10
6
x10
5
x10
4
n+9
n+8
x10
3
x10
2
x10
1
x10
0
x10
6
x10
5
x10
4
XFER (70)
#0002
n+8
HR 00
x10
3
x10
2
x10
1
x10
0
x10
6
x10
5
x10
4
Sign
HR 00
HR 01
n+5, bit 11
Direc-
tion
Direc-
tion
Data Preparation
Data must be prepared in the same manner as for normal execution of
TRANSFER DATA, except that only two words indicating the target position
are necessary.
Present Position
Preset Bit
word n+2, bit 15
Set this bit to 1 in order to use the preset function. If this bit is set to 0, the
beginning transfer number is set in bits 15-08 as described in Beginning
Word Number under 4–8–2 IR Area Settings.
Beginning word
Number
word n+3, bits 15-00
This number indicates the first of the two words to be transferred in as the
present position. The two words must be within one of the data areas desig-
nated for Data Preparation toward the beginning of 4–8–1 Normal Transfer.
Transfer Data
Section 4–8