70
Present
position
DM 1052
DM 1053
DM 1054
CCW
positioning axis
0
CW
Data set using TEACH is valid immediately and can be used for positioning
actions without turning off the power or transferring data. Note that data re-
written using the Programming Console is not valid until data has been trans-
ferred again.
4–7–1
IR Area Settings
In C200H PCs, IR words 100 to 199 are used for Special I/O Units. When a
Position Control Unit is used, they are allocated as I/O refresh areas. For a
detailed explanation, see 3–4 Data Configuration and Allocation. For a de-
tailed table of words and bits in the IR area, see Appendix D IR Area Alloca-
tions.
Present Position
When the no-origin flag is OFF, and pulse output is stopped at the position to
be taught, the present position is set in words n+8 and n+9.
TEACH Positioning
Action Number
word n+1, bits 15-08
Set an integer between 00 and 19. The number set here indicates the posi-
tioning action under START for which the present position is to be set as the
target position.
TEACH Command Bit
word n, bit 09
TEACH is executed when this bit is ON.
Teach
Section 4–7