![Omron SYSMAC C200H-NC111 Скачать руководство пользователя страница 69](http://html1.mh-extra.com/html/omron/sysmac-c200h-nc111/sysmac-c200h-nc111_operation-manual_742430069.webp)
58
then begins searching in the search direction.
Origin proximity signal
1
0
1
0
Origin signal
Proximity speed
Origin (Stop)
Search direction (CCW)
CCW
CW
Positioning axis
ORIGIN SEARCH (Begin)
Example 3
When reaching the CW or CCW limit during ORIGIN SEARCH, the Unit
pauses for 0.5 s, returns beyond the activation point for the origin proximity
signal, and then begins searching in the search direction.
Origin proximity signal
1
0
1
0
Origin signal
Proximity speed
Origin (Stop)
Search direction (CCW)
CCW
CW
Positioning axis
ORIGIN SEARCH (Begin)
Deceleration
Deceleration
Acceleration
Acceleration
CW limit
High speed
0.5 s
Search Patterns Without
Origin Proximity Signal
When an origin proximity signal is not present, only the ORIGIN SEARCH
proximity speed is used for ORIGIN SEARCH. This affects the three search
Origin Search
Section 4–2